| BATTERY MODULE SPECIFICATION | BAT-SNA48 |
| Usable Energy (100% depth of discharge) | 5120 Wh |
| Continuous Output Power (Charge/Discharge) – for a single module | 2560/5000 W |
| Continuous Output Power (Charge/Discharge) – for multiple modules | 5000/5000 W |
| Peak Roundtrip Efficiency | >93 % |
| Warranty | 10 years |
| Voltage Range | 40 – 57 Vdc |
| Communication Interfaces | RS485 between modules, RS485 between inverter |
| Modules per Inverter | Up to 5 connected in parallel |
| Battery Type | LFP |
| Supporting Inverter Models | See technical specifications |
| STANDARD COMPLIANCE | |
| Safety (Cell level) | GB/T 31485—2015, IEC62619; UN38.3 |
| Safety (Module level) | GBT 36276-2018 ,UN38.3; IEC62619; IEC63056; IEC62040-1; VDE-AR-E 2510-50(3) |
| Emissions | IEC61000-6-1; IEC61000-6-2; IEC61000-6-3; IEC61000-6-4; 61000-3-12 |
| MECHANICAL SPECIFICATIONS | |
| Dimensions (W x H x D) | 820 x 442 x 170 mm |
| Weight | 127 kg |
| Mounting | All-In-One |
| Operating Temperature(4) Charge/Discharge | 0 to +50/-30 to +50 |
| Storage Temperature (12 months between recharge) | -20 to +45 °C |
| Maximum Altitude | 2000 m |
| Enclosure Protection | IP54 |
| Cooling | Air cooling |
| Noise (at 1m distance) | <60 dBA |